Optima™ PDUs
Product SelectorMPD 125-052
2U PDU Specs
Power Outlets
Front Panel
None
Rear Panel
(2) 5-20R, 120V
(6) 5-20R, 120V (S)
(3) L6-20R, 208V (S)
(6) 5-20R, 120V (S)
(3) L6-20R, 208V (S)
Other Panels
None


Power Input
Voltage
120/208 Vac
Phase
3-Phase Wye
Frequency
50/60 Hz
Max Current
30 Amps
Max Load
2.88 KVA, 8.63 KVA
Connection
L21-30P, 15 ft cord, 5-wire 10 ga, SO jacket (Front panel)
Voltage Monitor
None
Current Monitor
None

Power Protection
Spike/Surge
Yes
EMI Filter
Yes
Over Current
(1) 30A Main Breaker
(4) 20A Circuit Breaker
(4) 20A Circuit Breaker
Remote, Interlocks, and Environment Sensors
Local EPO
None
Remote EPO Type
N.O./N.O. (view Commander UCP panels)
Interlocks
0
Temperature
0
Humidity
0
Communications and Interfaces
Display
None
Serial
None
Ethernet
None
Protocols
None
Physical
Layout
2U
Dimensions
2U x 19" W x 12.5" D
Materials
Chassis: Steel
Finishes
Chassis: Zinc plated Gold
FrontPanel: Zinc plated Gold
FrontPanel: Zinc plated Gold
Operating Conditions
Temperature
32° to 122° Fahrenheit
Humidity
5% to 85% Relative Humidity
Elevation
6,562 feet
Conformance
Warranty
See warranty page for details
Conformances
no specific certifications
Notes:
Read the product Feature Descriptions for important details. Specifications are subject to change without notice.
[1] Certain details of the circuitry may only be revealed by the schematic (available separately).
[2] All ratings of amps are maximum. See model details for deratings.
[3] Feature codes: Enet = Ethernet, VMtr = volts meter, AMtr = amps meter, rEPO = remote EPO, Seq = outlet sequencing, EMI = EMI filter, Srg = surge suppression
[4] Outlet Codes: (S) = switched, (V) = monitored voltage, (A) = monitored amps. Check Feature Descriptions for details.