800-462-7929 • sales@marway.com

Optima PDUs

Product Selector

MPD 125-042
2U PDU Specs

Power Outlets
Front Panel
None
Rear Panel
(2) 5-20R, 120V
(6) 5-20R, 120V (S)
(3) L5-20R, 120V (S)
Other Panels
None
Icon of outlet
5-20R
Icon of outlet
L5-20R
Power Input
Voltage
120/208 Vac
Phase
3-Phase Wye
Frequency
50/60 Hz
Max Current
30 Amps
Max Load
2.88 KVA, 8.63 KVA
Connection
L21-30P, 15 ft cord, 5-wire 10 ga, SO jacket (Front panel)
Voltage Monitor
None
Current Monitor
None
Icon of inlet
L21-30P
Power Protection
Spike/Surge
Yes
EMI Filter
Yes
Over Current
(1) 30A Main Breaker
(4) 20A Circuit Breaker
Remote, Interlocks, and Environment Sensors
Local EPO
None
Remote EPO Type
Interlocks
0
Temperature
0
Humidity
0
Communications and Interfaces
Display
None
Serial
None
Ethernet
None
Protocols
None
Physical
Layout
2U
Dimensions
2U x 19" W x 12.5" D
Materials
Chassis: Steel
Finishes
Chassis: Zinc plated Gold
FrontPanel: Zinc plated Gold
Operating Conditions
Temperature
32° to 122° Fahrenheit
Humidity
5% to 85% Relative Humidity
Elevation
6,562 feet
Conformance
Warranty
See warranty page for details
Conformances
no specific certifications

Notes:

Read the product Feature Descriptions for important details. Specifications are subject to change without notice.

[1] Certain details of the circuitry may only be revealed by the schematic (available separately).

[2] All ratings of amps are maximum. See model details for deratings.

[3] Feature codes: Enet = Ethernet, VMtr = volts meter, AMtr = amps meter, rEPO = remote EPO, Seq = outlet sequencing, EMI = EMI filter, Srg = surge suppression

[4] Outlet Codes: (S) = switched, (V) = monitored voltage, (A) = monitored amps. Check Feature Descriptions for details.